Overview


ETC6003 is an integrated burner management system for modulating dual gas burners that operate on two distinct gas fuels. It is designed for applications that switch between separate gas sources, such as natural gas and waste gas, and it is not intended for blended firing. The compact controller integrates key safety, modulation, and ratio control functions for both new installations and retrofit work.

Core functions


  • Manages modulating dual gas burners operating on two distinct gas fuels, supporting single and mixed fuel profiles
  • Switches between separate gas sources, maintaining controlled combustion performance during fuel transitions
  • Executes integrated burner start-up sequencing functions and timings, including ignition control
  • Provides flame supervision using supported IR, UV, photocell, or ionization flame detection interfaces
  • Performs integrated PID modulation and air-fuel ratio control, including programmable fuel-air profile curve sets
  • Integrates safety and proving functions for dual gas systems, including gas valve proving, leak detection, and fuel safety valve control and proving

Key technical features


  • Suitable for dual gas burners
  • Integrated burner start-up sequence functions and timings
  • Integrated ignition control
  • IR, UV, photocell and ionization flame detector support
  • Control of two variable speed drives for combustion air and fuel pump control
  • Up to 10 rotary servomotors can be assigned
  • Rotary servomotors positioning accuracy of ±0.1°
  • Fuel safety valve control and proving for two gas delivery systems
  • Up to 4 fuel-air ratio profile curve sets can be programmed
  • Communications protocol options include RS-485, Profibus and Modbus RTU

Options and customization


  • Optional fan speed control via variable frequency drive (VFD)
  • Oxygen trim option using a dedicated ETC oxygen probe and interface
  • Communications interface selection via RS-485, Profibus or Modbus RTU (as required)
  • Options for oil firing or boiler water control expansion

Typical applications


  • Dual gas burner systems that alternate between a primary gas and a secondary waste gas source
  • Industrial sites using natural gas with available waste gas fuels such as biogas, refinery off-gas, or landfill gas
  • Retrofit upgrades where integrated dual gas safety proving, flame supervision, and ratio control are required in a compact controller

Documents & Downloads


  • InnoBurn - Company Profile TR 🇹🇷
  • ETC6003 - Product Catalogue TR 🇹🇷

  • InnoBurn - Company Profile EN 🇺🇸
  • ETC6003 - Product Catalogue EN 🇺🇸

  • InnoBurn - Company Profile AR 🇸🇦
  • ETC6003 - Product Catalogue AR 🇸🇦

 Would you like to know more ? 

If you need further information, samples, a quote or advice for a project, please fill out the form below and we would be happy to help.