Overview
ETC6212 is a daughter board expansion module for the ETC6000 series that adds boiler drum water level control plus boiler water quality monitoring. It integrates level, TDS, and temperature sensing with control, alarms, and outputs for safer and more efficient boiler operation in industrial environments.
Core functions
- Monitors boiler drum water level using dual 4-20 mA level probe inputs
- Supports single-, two-, and three-element feed-water control strategies
- Monitors boiler water quality via Total Dissolved Solids (TDS) sensing and temperature measurement
- Automates blowdown management based on time, measured TDS limits, or maximum time since the previous cycle
- Provides safety alarming via relay outputs for high and low water level conditions
- Interfaces with supervisory systems using an isolated 4-20 mA output for data retransmission
Key technical features
- Dual 4-20 mA level probe inputs for drum level measurement and redundancy
- Dedicated terminals for TDS probes (conductivity sensing)
- Dedicated terminals for PT100 temperature sensors
- Relay outputs for high and low water level alarms
- Isolated 4-20 mA analog output for integration with external monitoring and control systems
- Power supply: 24-230 VAC
- Operating ambient temperature range: 0°C to 60°C
- Environmental protection options: IP40 (standard indoor) and IP54 (enhanced protection for harsher environments)
- Single-element control mode for stable operating conditions
- Two-element control strategy incorporating steam flow rate measurement
- Three-element control strategy incorporating steam flow and feed water flow measurement
Options and customization
- Select the feed water strategy to match the plant needs: single-, two-, or three-element configuration
- Configure blowdown triggering method: time interval, measured TDS limit, or maximum allowable time since last blowdown
- Select the environmental protection variant according to installation conditions: IP40 or IP54
- Add compatible field instrumentation as required: 4-20 mA level probes, TDS probe, and PT100 temperature sensor
Typical applications
- Steam boiler drum level control where single-, two-, or three-element feed-water strategies are required
- Boiler rooms that need integrated TDS monitoring and automated blowdown to protect efficiency and equipment life
- Industrial installations requiring ETC6000 series integration and operator visibility via the ETC touch-screen HMI environment
Documents & Downloads
- InnoBurn - Company Profile (TR) 🇹🇷
- ETC6212 - Product Catalogue (TR) 🇹🇷
-
- InnoBurn - Company Profile (EN) 🇺🇸
- ETC6212 - Product Catalogue (EN) 🇺🇸
- InnoBurn - Company Profile (AR) 🇸🇦
- ETC6212 - Product Catalogue (AR) 🇸🇦
Would you like to know more ?
If you need further information, samples, a quote or advice for a project, please fill out the form below and we would be happy to help.